Edwards (2490027) Edwards signaling 2490027

$194.66

SKU: 2490027 Brand:

Edwards Signaling 2490027

Out of stock

The Edwards 2490027 is a 120 VAC primary to 26.4 VAC secondary power transformer used as a service / replacement part in Edwards fire alarm panels. First, note: this is a transformer — not a pull station, not a notification appliance, and not a stand-alone listed device. Specifically, it is designed as a component for the E-FSC502 conventional fire alarm panel (the FireShield Conventional 5-zone family). Therefore, it should be specified only as a like-for-like replacement when the original panel transformer fails.

What the Edwards 2490027 transformer does

This transformer steps standard 120 VAC building power down to the lower secondary voltage required by the panel’s internal power supply. As a result, the panel can drive its CPU, NAC outputs, and IDC supervision circuits from a regulated low-voltage rail. In addition, the design includes a thermal class rating suitable for continuous panel operation.

Verified specs

  • Function: AC step-down power transformer (panel service part)
  • Primary voltage: 120 VAC, 60 Hz
  • Secondary voltage: 26.4 VAC
  • Secondary current: ~4.25 A
  • Power capacity: ~111 W
  • Turns ratio: 283:70
  • Thermal class: 130°C
  • Application: replacement transformer for the Edwards E-FSC502 panel family

What this part is NOT

However, the 2490027 is not a complete fire alarm panel, an end-use signaling appliance, or a stand-alone UL-listed device. Therefore, agency listings (UL 864 etc.) live at the host panel level, not at the transformer part level. Furthermore, this is not a pull station — despite some catalog mis-tagging that lists it under pull-station search terms.

Installation notes

As a result, the 2490027 should only be replaced by a qualified fire alarm technician with the host panel powered down and locked out. Specifically, verify the host panel’s wiring diagram before swap-out. In addition, retain the original transformer for warranty or RMA purposes if applicable.

Need help selecting the right Edwards part? Call Life Safety Consultants at 1-888-557-0558 or email sales@lifesafetycom.com. Our team specializes in fire alarm and industrial signaling replacement parts.

Additional information

Weight 4 lbs
Dimensions 4 × 4 × 3 in
Condition

New

Manufacturers

Edwards

Part Type

Pull Station

View and Download Data Sheet