The Edwards 757-8A-SS25W is a 110-candela cone speaker-strobe in white, designed for 25 V fire-alarm audio risers. Specifically, the 110 cd rating meets the recommended intensity for sleeping-area notification per NFPA 72 and UL 1971. As a result, this appliance is the right pick for hotels, dormitories, assisted-living, and other sleeping-room applications.
First, the 757-8A-SS25W carries a 4-inch mylar cone speaker with sealed-back construction. Then a built-in DC blocking capacitor allows the panel to electrically supervise the audio distribution circuit. Therefore, the speaker is correctly supervised on a standard 25 V audio riser.
110 cd Strobe for Sleeping Areas
Furthermore, the integrated strobe is UL 1971-listed at 110 cd wall mount and 60 cd ceiling mount. In addition, it is UL 1638 / ULC S526-listed at 110 cd as a protective visual signaling appliance. As a result, this single appliance handles both public-mode hearing-impaired notification and the higher-intensity sleeping-room recommendation in one device.
Specifically, Edwards recommends that strobes in sleeping rooms be rated at least 110 cd. Therefore, the 757-8A-SS25W meets that recommendation directly without an external lens or shroud.
Wattage Taps and Sound Output
Also, the 757-8A-SS25W is field-selectable for ¼, ½, 1, or 2 watt operation. As a result, the installer can balance output against branch loading without changing devices.
Specifically, the cone speaker-strobe dBA output per tap (UL 1480 method) is:
- ¼ W — 78 dBA
- ½ W — 81 dBA
- 1 W — 84 dBA
- 2 W — 87 dBA
Synchronized Flash
Furthermore, the 757-8A-SS25W synchronizes at one flash per second. As a result, multiple strobes on the same circuit flash together when paired with an external synchronization source. Compatible sync sources include G1M-RM, SIGA-CC1S, SIGA-MCC1S, BPS6A, and BPS10A.
Cold-Weather Strobe Output
Specifically, the -8A series is rated 70.7 cd @ -35°C per UL (and @ -40°C per ULC) for outdoor cold-weather operation. Therefore, the appliance retains useful output across the temperature range when paired with a weatherproof box.
Operating Voltage
Furthermore, the speaker accepts 25 VRMS audio. Then the strobe runs on 16 to 33 VDC continuous (not pulsed). In addition, a diode allows full signal-circuit supervision.
Verified Specifications
- Strobe rating (wall): 110 cd (UL 1971)
- Strobe rating (ceiling): 60 cd (UL 1971)
- UL 1638 / ULC S526 rating: 110 cd
- Speaker driver: 4-inch mylar cone, sealed-back, 8-ohm voice coil
- Speaker voltage: 25 VRMS
- Speaker taps: ¼, ½, 1, 2 W
- Speaker frequency response: 250 to 13,000 Hz
- Strobe voltage: 16–33 VDC continuous
- Strobe current (110 cd): 180 mA @ 24 VDC typical / 329 mA @ 16 VDC RMS UL
- Flash rate: 1 fps synchronized
- Housing: Textured, color-impregnated engineered plastic (exceeds UL 94V-0)
- Color: White (red version is 757-8A-SS25)
- Lens: Clear LEXAN; ships with LKW-1 “FIRE” wall-mount markings
- Wire connections: Separate polarized terminals for speaker and strobe, #12 AWG (2.5 mm²) max
- Operating environment (indoor): 32–120°F (0–49°C), 85% RH @ 30°C
- Cold-weather strobe output: 70.7 cd @ -35°C UL / -40°C ULC
- Listings: UL 1971, UL 1638, UL 1480, ULC S526, ULC S541, MEA, CSFM, FM
- ADA compliant (Code of Federal Regulation Chapter 28 Part 36 Final Rule)
Mounting
Specifically, the 757-8A-SS25W flush-mounts to a standard North-American 4-inch square electrical box, 1½-inch deep, with a 1½-inch extension ring. Therefore, no separate trim plate is required. Also, surface mounting uses Edwards’s color-matched accessory boxes:
- 757A-SBW — indoor surface box, white
- 757A-BDFW — bi-directional mounting frame, white
However, the cone-type SS25W variant is rated for INDOOR use only. Therefore, outdoor or wet-location installations should use the re-entrant RS25 series with a 757A-WBW weatherproof box.
Lens Markings
The unit ships with “FIRE” wall-orientation markings. Therefore, ceiling-mount or alternate-language installations need an LKW or LKC lens kit (e.g., LKC-1 for ceiling “FIRE”, LKW-2 for “FEU”, LKW-3 for bilingual “FIRE/FEU”, LKW-4 for “SMOKE”, LKW-7 for “EMERGENCY”).
Order the Edwards 757-8A-SS25W
To order the Edwards 757-8A-SS25W, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 2 lbs |
|---|---|
| Dimensions | 5 × 6 × 5 in |
| Condition | New |
| Manufacturers | Edwards |
| Part Type | Strobe |