The Hochiki DCP-AMS is a single-action addressable manual pull station. An occupant initiates a fire alarm by pulling down on the handle.
First, the station communicates over Hochiki’s DCP protocol on the SLC loop. Then the address is programmable in onboard EEPROM. As a result, the panel identifies the exact pull-station location at activation.
Hochiki DCP-AMS Construction
The housing is made of 14 AWG cold-rolled steel painted with red enamel. In addition, the words “Fire Alarm” are embossed in 1/2″ tall contrasting-color text. Therefore the station meets standard wall-mount visibility requirements.
Key Specifications
- Activation: single-action — pull the handle down
- Operating voltage (SLC): 17 – 41 VDC
- Address: programmable in onboard EEPROM
- Status LED: bi-colored; blinks green during normal SLC communication
- Mounting: single-gang or 4″ square electrical box
- Reset: requires the CAT 30 key or a 1/8″ hex key (depending on model variant)
- Listings: UL Listed and CSFM Approved
- Single-action models meet ADA requirements when installed per code
When to Use the DCP-AMS
Furthermore, the DCP-AMS suits standard occupancy applications where a single-action pull is acceptable. For dual-action requirements, see the DCP-AMS-LP (Lift and Pull) variant.
Order or Get Application Help
Since 2002, Life Safety Consultants has been a trusted source for Hochiki addressable pull stations. To order the Hochiki DCP-AMS or get application guidance, call 1-888-557-0558. You can also email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 1.5 lbs |
|---|---|
| Dimensions | 3 × 5.5 × 5 in |
| Condition | New |
| Manufacturers | Hochiki |
| Part Type | Pull Station |