The Simplex 4098-9756 is an addressable duct smoke detector housing that uses TrueAlarm analog sensing to monitor for smoke in HVAC ducts. Unlike the simpler 4098-9755 (no relay), the 4098-9756 adds a supervised output for up to 15 remote PAM-SD relays under panel control — the relay can be activated manually from the panel or triggered by an alarm or other input. The factory-installed photoelectric sensor communicates analog values digitally over MAPNET II or IDNet (auto-select, one address per housing), with sensitivity selectable at the fire alarm control panel across 7 levels: 0.2% to 3.7% per foot of obscuration. Duct applications typically call for 2.5%/ft or higher due to dilution.
Key Features
- Communication: MAPNET II or IDNet auto-select, 2-wire, one address per housing
- Sensor: Factory-installed TrueAlarm photoelectric (analog, addressable)
- Sensitivity range: 0.2% to 3.7%/ft obscuration, 7 levels, panel-selectable
- Relay output: Supervised, for up to 15 remote PAM-SD relays
- Relay control: Under panel control — manual or alarm-triggered
- Input voltage (4098-9756): 18–32 VDC (24 VDC nominal) from fire alarm power supply
- Standby current: 2.4 mA @ 24 VDC
- Alarm current: 15 mA @ 24 VDC + 15 mA per additional PAM-SD relay
- PAM-SD relay contacts: 7A @ 28 VDC; 10A @ 120 VAC (single Form C)
- Airflow range: 300 to 4,000 ft/min (91–1,220 m/min)
- Duct size: minimum 8" (203 mm) square or 18" (457 mm) round
- Wiring: Terminal blocks, 18 to 12 AWG
- Diagnostics: Red Alarm/Trouble LED; Yellow LED for relay control trouble (4098-9756 only)
- Test: Magnetic test feature; test ports for functional smoke test with cover in place
- Temp range (UL): 32° to 100°F (0° to 38°C); Operating: 32° to 122°F
- Humidity: 10–95% RH non-condensing
- Housing: Black base with clear cover for visual inspection
- Dimensions: 13 × 11 × 7 in; Weight: 6 lbs
- Catalog#: 0631149
- UL listed Standard 268A; CSFM; FM; MEA (NYC); ULC (model 4098-9756C)
Compatible Panels
- Simplex 4100ES (IDNet)
- Simplex 4010ES (IDNet)
- Simplex 4100+ (MAPNET II)
- Any Simplex panel with MAPNET II or IDNet loop support
Related Products
- 4098-9755 — Basic duct housing, no relay, MAPNET II/IDNet powered (no separate 24 VDC required)
- 4098-9686 — 4-wire duct detector housing
- 4098-9714 — TrueAlarm photoelectric sensor head (compatible)
- 2098-9808 — Remote status/alarm LED
- 2098-9806 — Remote test station with LED
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 6 lbs |
|---|---|
| Dimensions | 13 × 11 × 7 in |
| Condition | New |
| Part Type | Duct Detector / Housing, Photoelectric, Sensor |
| Manufacturers | Simplex |
| Compatible Panels | Simplex 4100ES, Simplex 4010ES, Simplex 4100+ (MAPNET II), any panel with MAPNET II or IDNet loop |
| Cross Reference | 0631149, 4098-9756, 4098-9756C (ULC) |
| Specification | MAPNET II/IDNet auto-select, 0.2-3.7%/ft sensitivity (7 levels), 18-32 VDC (24V nom), 2.4mA standby, 15mA alarm, PAM-SD relay 7A@28VDC, 300-4000 ft/min airflow, min 8in sq / 18in round duct, 18-12 AWG, UL 268A |