Simplex (4098-9756) TrueAlarm Duct Sensor Housing 0631149

$259.00

SKU: 4098-9756 Brand:

TrueAlarm Duct Sensor Housing 0631149

2 in stock

The Simplex 4098-9756 is an addressable duct smoke detector housing that uses TrueAlarm analog sensing to monitor for smoke in HVAC ducts. Unlike the simpler 4098-9755 (no relay), the 4098-9756 adds a supervised output for up to 15 remote PAM-SD relays under panel control — the relay can be activated manually from the panel or triggered by an alarm or other input. The factory-installed photoelectric sensor communicates analog values digitally over MAPNET II or IDNet (auto-select, one address per housing), with sensitivity selectable at the fire alarm control panel across 7 levels: 0.2% to 3.7% per foot of obscuration. Duct applications typically call for 2.5%/ft or higher due to dilution.

Key Features

  • Communication: MAPNET II or IDNet auto-select, 2-wire, one address per housing
  • Sensor: Factory-installed TrueAlarm photoelectric (analog, addressable)
  • Sensitivity range: 0.2% to 3.7%/ft obscuration, 7 levels, panel-selectable
  • Relay output: Supervised, for up to 15 remote PAM-SD relays
  • Relay control: Under panel control — manual or alarm-triggered
  • Input voltage (4098-9756): 18–32 VDC (24 VDC nominal) from fire alarm power supply
  • Standby current: 2.4 mA @ 24 VDC
  • Alarm current: 15 mA @ 24 VDC + 15 mA per additional PAM-SD relay
  • PAM-SD relay contacts: 7A @ 28 VDC; 10A @ 120 VAC (single Form C)
  • Airflow range: 300 to 4,000 ft/min (91–1,220 m/min)
  • Duct size: minimum 8" (203 mm) square or 18" (457 mm) round
  • Wiring: Terminal blocks, 18 to 12 AWG
  • Diagnostics: Red Alarm/Trouble LED; Yellow LED for relay control trouble (4098-9756 only)
  • Test: Magnetic test feature; test ports for functional smoke test with cover in place
  • Temp range (UL): 32° to 100°F (0° to 38°C); Operating: 32° to 122°F
  • Humidity: 10–95% RH non-condensing
  • Housing: Black base with clear cover for visual inspection
  • Dimensions: 13 × 11 × 7 in; Weight: 6 lbs
  • Catalog#: 0631149
  • UL listed Standard 268A; CSFM; FM; MEA (NYC); ULC (model 4098-9756C)

Compatible Panels

  • Simplex 4100ES (IDNet)
  • Simplex 4010ES (IDNet)
  • Simplex 4100+ (MAPNET II)
  • Any Simplex panel with MAPNET II or IDNet loop support

Related Products

  • 4098-9755 — Basic duct housing, no relay, MAPNET II/IDNet powered (no separate 24 VDC required)
  • 4098-9686 — 4-wire duct detector housing
  • 4098-9714 — TrueAlarm photoelectric sensor head (compatible)
  • 2098-9808 — Remote status/alarm LED
  • 2098-9806 — Remote test station with LED

For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com

Additional information

Weight 6 lbs
Dimensions 13 × 11 × 7 in
Condition

New

Part Type

Duct Detector / Housing, Photoelectric, Sensor

Manufacturers

Simplex

Compatible Panels

Simplex 4100ES, Simplex 4010ES, Simplex 4100+ (MAPNET II), any panel with MAPNET II or IDNet loop

Cross Reference

0631149, 4098-9756, 4098-9756C (ULC)

Specification

MAPNET II/IDNet auto-select, 0.2-3.7%/ft sensitivity (7 levels), 18-32 VDC (24V nom), 2.4mA standby, 15mA alarm, PAM-SD relay 7A@28VDC, 300-4000 ft/min airflow, min 8in sq / 18in round duct, 18-12 AWG, UL 268A