The KIDDE COMMERCIAL FX-SLC2 is a Dual SLC Interface Card for the Kidde FX-1000 intelligent fire alarm control panel. Specifically, it adds two signaling line circuits in a single card.
First, the card provides 500 device addresses total — 250 per loop. Then, each loop splits into 125 detectors and 125 modules. As a result, one FX-SLC2 doubles the loop count compared to the single-loop FX-SLC1.
In addition, the FX-1000 ships with one onboard SLC and supports up to four loops via FX-SLC1 and FX-SLC2 cards. Furthermore, a fully expanded FX-1000 reaches 1,000 addressable points.
Key Features of the KIDDE COMMERCIAL FX-SLC2 Dual SLC Interface Card
- Two signaling line circuits per card
- 500 device addresses total (250 per loop)
- Each loop supports 125 detectors and 125 module addresses
- Class B, Class A, and Class X wiring per loop (Style 4, 6, 7)
- Up to 64 isolators per loop (bases plus modules)
- Status LEDs for device communication and per-loop fault
- Installs in FX-1000 primary or secondary card slot
- Field labels included to mark the correct SLC numbers on the panel
Specifications
- Wiring: Class B, Class A, or Class X (Style 4, 6, and 7)
- Operating voltage: 24 VDC
- Operating current (fully loaded): standby 45 mA; alarm 70 mA
- SLC loop voltage: 20 V peak-to-peak max.
- Maximum total loop resistance: 66 Ω (per loop)
- Maximum total loop capacitance: 0.5 µF (per loop)
- Isolators: 64 max per loop (bases plus modules)
- Loop max detector standby current: 1.5 mA (consult panel UL compatibility list for device limits)
- Compatibility ID: 100, S10A, S11A
- Terminal rating: 12 to 18 AWG (0.75 to 2.5 mm²)
- Operating temperature: 32 to 120°F (0 to 49°C)
- Relative humidity: 0 to 93% noncondensing at 90°F (32°C)
- Maximum wiring length: 20,000 ft per data loop
- Documented in Kidde FX-Series Quick Reference K85000-0373 and FX-64/FX-1000 Technical Reference Manual P/N 3102352-EN
FX-1000 Expansion Path
First, the FX-1000 includes one onboard 250-device SLC. Then, adding one FX-SLC1 raises capacity to 500 devices on two loops. In addition, an FX-SLC2 raises capacity to 750 devices on three loops, or 1,000 devices when paired with another FX-SLC1. As a result, the panel scales in 250-device steps up to the 1,000-device, four-loop maximum.
Order or Get Application Help
Life Safety Consultants stocks the FX-SLC2 alongside the FX-1000 panel, single-loop FX-SLC1 cards, and the full Kidde addressable device lineup. To order the KIDDE COMMERCIAL FX-SLC2 or plan FX-1000 expansion, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.2 lbs |
|---|---|
| Dimensions | 5.2 × 3.8 × 3 in |
| Condition | New |
| Manufacturers | Kidde |
| Part Type | Strobe |