The Potter Electric Signal PAD200-DUCT Duct Detector represents a critical life safety solution for comprehensive fire detection within HVAC air handling systems across commercial and institutional facilities. Engineered to UL 7th Edition standards, this advanced detector provides reliable smoke detection in air ducts, enabling early warning and rapid response to potential fire hazards in ventilation networks.

Designed for seamless integration with addressable fire alarm control panels, the PAD200-DUCT monitors airflow between 100-4,000 feet per minute, making it versatile for diverse commercial building configurations. Its robust photoelectric sensing technology can detect both obscuration and particulate smoke signatures, ensuring precise and consistent performance across varying environmental conditions.

Key Features

  • UL Listed to 7th Edition standards for comprehensive compliance with NFPA 72 requirements
  • Compatible with most major addressable fire alarm control panels and communication protocols
  • Advanced photoelectric sensing technology with adjustable sensitivity settings
  • Rugged, compact design suitable for challenging HVAC installation environments
  • Wide operational airflow range from 100-4,000 feet per minute
  • Integrated LED indicator for immediate visual status confirmation

Specifications

  • Operating Voltage: 24VDC nominal
  • Standby Current: 250µA maximum
  • Alarm Current: 6-10mA
  • Operating Temperature: 32°F to 120°F
  • Relative Humidity: 10-93% non-condensing

Typical installation contexts include commercial office complexes, healthcare facilities, educational institutions, data centers, and industrial environments where continuous air handling system monitoring is critical. The PAD200-DUCT provides essential early detection capabilities, helping prevent potential fire spread through HVAC ductwork and supporting comprehensive building life safety strategies.

Compatible with standard NFPA 72 fire alarm installation practices and meeting rigorous UL 268 smoke detector standards, this duct detector represents a professional-grade solution for advanced fire detection and notification systems.

For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com