TrueAlarm 4-wire Duct Detector Housing w/relay output

Out of stock

Simplex 4098-9686 4-wire Duct Detector Housing w/ relay output  0631139

Life Safety Consultants is here to ensure your fire and smoke detectors are always in working order. That’s why we offer a wide range of replacement parts and components like the Simplex Duct Housing 4-Wire Model 4098-9686 which provides basic smoke detection for applications that require a remote relay.  Order yours today and we’ll ship your Simplex 4-wire Duct Housing 4098-9686 in no time.  If you would like to learn more about this part or any of the other products we offer, contact the Life Safety Consultants team at (888) 557-0558 or email us at:  sales@lifesafetycom.com

 

 

Additional information

Weight 5 lbs
Dimensions 13 × 11 × 7 in
Condition

New

Manufacturers

Simplex

 

 

 

 

 

Features

  • Compact air duct detector housing with clear cover to monitor for the presence of smoke**
  • Includes factory installed TrueAlarm photoelectric smoke detector and features:
    • On-board TrueAlarm sensitivity drift compensation and dirt accumulation tracking
    • Multi-function status LED indicator
    • Magnetic test that initiates an alarm and provides detailed diagnostic information
    • Clear cover allowing visual inspection
    • Test ports provide functional smoke testing access with cover in place
  • UL listed to Standard 268A
  • Model availability:
    • 4098-9685, 2-Wire standard operation
    • 4098-9688, 2-Wire with supervised control for a single remote relay (relay included)
    • 4098-9686, 4-Wire operation with supervised control for multiple remote relays (includes one remote relay)
  • Mounts to rectangular ducts or round ducts
    • Minimum size is 8” (203 mm) square or 18” (457 mm) diameter
  • Magnetically operated functional test:
    • Initiates alarm and displays dirt accumulation status using the detector status LED
    • Assists with maintenance priorities by categorizing detector status and identifying dirty detectors
  • Sampling tubes (ordered separately):
    • Available in multiple lengths to match duct size
    • Installed and serviced with housing in place
  • Remote module options (ordered separately):
    • Red alarm LED (4098-9830)
    • Test stations with LED(s) and keyswitch (refer to page 2 for compatibility)
    • Relays for remote control applications