The SigCom VECP-25 is a 25 Watt voice evacuation control panel, not a speaker. It adds voice evacuation capability to an existing fire alarm system without replacing the FACP. In other words, it connects directly to any addressable or conventional panel. Activation comes from a 24 VDC polarity-reversing NAC circuit or a supervised dry contact.
A built-in digital message unit provides 60 seconds of pre-recorded voice messaging. It includes two standard voice messages and four field-selectable alert tones. In addition, a supervised integral microphone allows live paging that overrides recorded messages. An optional DVS-RM/B supervised remote microphone is also available.
SigCom VECP-25 Speaker Circuits and Power
The high-efficiency Class D amplifier delivers 25 Watts of total output. It drives four supervised speaker circuits, wired Class A (Style Z) or Class B (Style Y). Furthermore, loop voltage is field-selectable between 25 and 70.7 Vrms. Digital signal meters display the power and voltage output on the speaker circuits. Common alarm and trouble Form-C relays signal external equipment.
Specifications
- Output power: 25 Watts total (sinusoidal, RMS); 25 or 70.7 Vrms, field selectable
- Speaker circuits: 4, Class A (Style Z) or Class B (Style Y); 10 KOhm EOL, power limited
- Primary activation: reverse-polarity NAC input, 10–30 VDC, 2 mA max
- Auxiliary message inputs: 2, supervised N.O. dry contacts for non-fire messages
- Auxiliary audio input: telephone/paging interface, 1 Vrms max, non-fire use
- Common relays: alarm and trouble, Form-C, 30 VDC at 1 A resistive
- AC power: 120 VAC, 60 Hz, 2 A; internal 24 VDC supply and battery charger
- Cabinet: dead-front, locked; 20″H x 15-3/4″W x 5″D; surface or flush mount, indoor
- Temperature: 32°F to 120°F (0°C to 49°C); humidity 90% max, non-condensing
- Listings: UL 864 (9th Ed.) Control Units and UL 1711 Amplifiers for Fire Protective Systems
Typical applications include schools, theaters, places of worship, offices, restaurants, and military facilities. Likewise, the auxiliary audio input lets the panel double as an industrial paging system.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Browse Related Products
Additional information
| Weight | 5.5 lbs |
|---|---|
| Dimensions | 20 × 15.8 × 5 in |
| Condition | New |
| Manufacturers | SigCom |
| Part Type | Speaker |
| Compatible Panels | SigCom VECP series |
| Cross Reference | VECP-50, DVS-RM/B |
| Specification | 25W output, pre-recorded message storage, live mic input |