HOCHIKI (HPS-SAK-PSK CAT 30) P/S Single Action, Key Lock W/ Cat 30 Ke

$50.09

SKU: HPS-SAK-PSK CAT 30 Brand:

P/S SINGLE ACTION, KEY LOCK W/ CAT 30 KE

37 in stock

The Hochiki HPS-SAK-PSK is a manual pull station for conventional fire alarm systems. Specifically, it is the single-action, key-locked, pre-signal variant with the CAT 30 key. As a result, a building occupant can pull the lever to trigger a fire alarm. Authorized staff with a CAT 30 key can also reset or test the station without removing it from the wall.

Application Notice

This is a MANUAL PULL STATION, not a power supply. The “P/S” in the abbreviated SKU stands for Pull Station. In addition, the “PSK” suffix denotes the Pre-Signal Key variant — designed for facilities that use NFPA 72 pre-signal alarm sequencing, where staff investigate before general alarm.

Verified Specifications

  • Type: Manual pull station, single action, pre-signal variant
  • Key: CAT 30 (industry standard fire alarm key)
  • Construction: solid die cast housing, glossy red finish
  • Back switch plate: plated steel
  • Switch rating: 10 Amps at 120 VAC, SPST Form A contacts
  • Connection: terminal block
  • Glass break rod: included
  • Listings: UL, California State Fire Marshal
  • Made in USA
  • Product code: 0600-01455

Pre-Signal Operation

Pre-signal pull stations differ from standard pull stations. Specifically, a pull at the lever sends an investigation signal to the fire alarm control panel. Then, authorized staff have a defined window to investigate the activation. If the alarm is verified, an authorized user inserts the CAT 30 key to trigger general alarm. As a result, the building avoids unnecessary full evacuation during investigation.

Pre-signal sequencing must be approved by the Authority Having Jurisdiction (AHJ). Furthermore, NFPA 72 requires specific procedures and timing for pre-signal use.

HPS Series Family

The Hochiki HPS Series comes in multiple variants. These include single action (SAH), single action with key lock (SAK), dual action (DAH), and Spanish-language dual action (DAH-S). The HPS-SAK-PSK adds the Pre-Signal Key feature to the SAK base.

Order or Get Application Help

Life Safety Consultants has stocked Hochiki conventional fire alarm devices since 2002. To order the Hochiki HPS-SAK-PSK CAT 30 pull station or confirm pre-signal AHJ requirements, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.

For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com

Additional information

Weight 1.5 lbs
Dimensions 5.5 × 5 × 3 in
Condition

New

Manufacturers

Hochiki

Part Type

Power Supply

View and Download Data Sheet