The Edwards SIGA-MCC1 is a single-input signal module for Signature Series fire alarm systems. It is the UIO plug-in version, and it functions identically to the SIGA-CC1. Specifically, it connects a supervised Class B signal or telephone circuit to its power input. As a result, the loop controller can switch that circuit on command.
Edwards SIGA-MCC1 function and personality codes
This module drives one riser, so an installer selects its role with a personality code. First, Code 5 configures it for 24 VDC signal power or 25/70 VRMS audio evacuation. Then, Code 6 configures it for firefighter telephone service with a built-in ring-tone generator. Therefore, no separate ring-tone circuit is required.
The SIGA-MCC1 plugs into UIO2R, UIO6R, or UIO6 motherboards. In addition, electronic addressing and automatic device mapping simplify commissioning. A green LED flashes when polled, and a red LED flashes when active.
Specifications
- Operating voltage: 15.2 to 19.95 VDC (19 VDC nominal)
- Operating current: 223 µA standby, 100 µA active
- Output rating: 2 A at 24 VDC, 50 W at 25 V audio, 35 W at 70 V audio
- Operating temperature: 32 to 120°F (0 to 49°C)
- Construction: high-impact engineering polymer
- Agency listings: UL, ULC, CSFM, MEA, FM
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.2 lbs |
|---|---|
| Dimensions | 5 × 5 × 2 in |
| Condition | New |
| Manufacturers | Edwards |
| Part Type | Relay Module |