KIDDE (VM-SLC) Loop Expansion, VM systems, 250 analog a

$587.99

SKU: VM-SLC Brand:

Loop Expansion, VM systems, 250 analog a

14 in stock

The Kidde VM-SLC Signaling Line Circuit card adds one Signature loop to a VM Series fire alarm control panel. As a result, the panel’s device capacity expands without rewiring the system.

Specifically, the VM-SLC plugs into a slot on the VM-CPU main board. Then, the new loop supports up to 125 detectors plus 125 modules. Furthermore, the card provides resettable 24 VDC for powering conventional two-wire smoke detectors through V-Series modules.

Install one VM-SLC for a second SLC on the CPU. In addition, install another VM-SLC on a VM-SLCXB expander to reach the panel’s four-loop maximum.

Key Features of the Kidde VM-SLC Card

  • One Class B (Style 4) or Class A (Style 6) Signature loop per card
  • 250 addressable points: 125 detectors + 125 modules
  • Resettable 24 VDC smoke power (85 mA) for two-wire detectors
  • 1.0 A resettable or continuous 24 VDC aux power output
  • Plug-in install on the VM-CPU main board
  • Pairs with the VM-SLCXB expansion card for loops 3 and 4

Specifications

  • Operating voltage: 24 VDC nominal
  • Standby current (full loop, second loop on CPU): 120 mA
  • Alarm current (full loop, second loop on CPU): 132 mA
  • Loop capacity: 125 detectors + 125 modules per circuit
  • Loop resistance: 100 Ω max.
  • Loop capacitance: 0.5 µF max.
  • Smoke-power output: 24 VDC at 85 mA
  • Aux power: 24 VDC, 1.0 A per circuit, 1.0 A total
  • Wire size: 18–12 AWG (0.75–2.5 mm²)
  • Operating environment: 32 to 120°F (0 to 49°C), 0–93% RH non-condensing

Selecting the Right SLC Card

For circuits with up to 90 isolators, use the standard VM-SLC. However, for circuits with more than 90 isolators, choose the VM-SLC-HC high-capacity variant. Furthermore, GSA-series module bases all operate on the same 24 VDC smoke-power feed.

Order or Get Application Help

Life Safety Consultants stocks the full VM Series catalog. To order the Kidde VM-SLC or to confirm panel loop slot availability, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.

For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com

Additional information

Weight 0.5 lbs
Dimensions 12 × 4 × 5 in
Condition

New

Manufacturers

Kidde

Part Type

Module

View and Download Data Sheet