The Pyrotronics ZU-35 is a legacy Cerberus Pyrotronics / Siemens System 3 dual zone module. Its factory part number is 500-888583.
What the Pyrotronics ZU-35 Does
First, the module provides two supervised initiating circuits in a single System 3 slot. Then, each circuit accepts a mix of ionization or photoelectric detectors plus shorting-contact devices. Specifically, pull stations and thermal devices can share a circuit with detectors.
In addition, the ZU-35 supports either NFPA Style D (Class A) or Style B (Class B) wiring. As a result, installers can match the existing System 3 wiring topology without rework.
Alarm Behavior and System 3 Integration
When a device on either circuit activates, the module locks into alarm. Then the System 3 panel runs its programmed sequence. For example, the panel may sound audibles, recall elevators, close doors, or shut down HVAC.
Also, a red Alarm LED and a yellow Trouble LED on the module face show per-circuit status at a glance. Furthermore, the module interconnects to the System 3 rail via a ten-pin plug and harness.
Condition
This Pyrotronics ZU-35 is sold reconditioned with a one-year warranty. It is intended for maintaining or repairing existing System 3 installations. Verify the 500-888583 catalog marking on receipt before installation.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 1 lbs |
|---|---|
| Dimensions | 2 × 4 × 1.5 in |
| Condition | Reconditioned w/ one year warranty ! |
| Manufacturers | Siemens |
| Compatible Panels | Siemens System 3 |
| Compatible Bases | N/A |
| Cross Reference | 500-888583, ZU-35, ZU35 |
| Two supervised initiating circuits; supports up to 30 detectors per zone; Class A or Class B wiring; LED indicators per zone; 0-49 deg C operating range; UL listed; FM approved; Dimensions | 2x4x1.5 in, Weight: 1 lb |