The Edwards SIGA-270L is a single-action manual fire alarm pull station from the Signature Series 270 family. It is identical to the SIGA-270 mechanically and electrically, except the front plate is marked “LOCAL ALARM” instead of “FIRE ALARM”. Use the SIGA-270L where the pull station signals a local annunciator or evacuation zone rather than a general building alarm.
How the Edwards SIGA-270L works
First, a single pull on the handle closes a normally-open dry-contact switch. Then the integrated Signature input module supervises the switch and reports the alarm to the loop controller. As a result, the station latches in alarm until reset with the supplied key.
Construction
The body is cast zinc with a steel backplate. The station finish is red with white lettering. In addition, a replaceable glass rod (USA P/N 276-GLR, 20-pack; Canada P/N 27165, 12-pack) breaks on activation to provide tactile feedback. The personality code is factory-set to 1 for alarm-latching operation.
Electrical specifications
Operating voltage range: 15.2 to 19.95 VDC. Standby current: 250 µA. Activated current: 400 µA. Operating temperature 32 to 120 °F (0 to 49 °C); humidity 0 to 93% RH; storage -4 to 140 °F.
Mounting
The SIGA-270L mounts to a North American 2-1/2 in deep 1-gang box, or a standard 4 in square box 1-1/2 in deep with a 1-gang cover. For surface mount, order accessory box 27193-10 (cream) or 27193-11 (red) separately. Terminal blocks accept 12, 14, 16, or 18 AWG; sizes 16 and 18 preferred.
Compatibility
Requires a Signature Loop Controller. Compatible with EST3 and EST3x panels, and with iO64 and iO500 panels using Signature Series devices.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 1 lbs |
|---|---|
| Dimensions | 5 × 3.5 × 3.5 in |
| Condition | New |
| Manufacturers | Edwards |
| Part Type | Pull Station |