The Simplex 4605-7401, also known as the 565-802 board, is a 24-point programmable input/output (I/O) module for the Simplex 4010 addressable fire alarm control panel. Each of the 24 I/O points is individually selectable as either an input or an output. Four input types are supported: unsupervised switch, supervised for open, supervised for open or short, and monitored three-position H.O.A. (hand-off-auto). Outputs are rated 24 V at 75 mA each (1.8 A total maximum at 32 VDC) and are selectable for continuous on, slow flash, or fast flash. The 4605-7401 communicates with the 4010 panel via N2 serial communications; up to six total annunciator modules are supported per system. Input supply voltage is 18–32 VDC; module operating current is 60 mA at 24 VDC. Wiring connections accept 18–14 AWG wire. UL listed to Standard 864, ULC, CSFM Listed, FM Approved, MEA (NYC) accepted.
Key Features
- 24 individually selectable I/O points per module
- Output rating: 24 V at 75 mA each; 1.8 A total max at 32 VDC
- Input voltage: 18–32 VDC
- Operating current: 60 mA at 24 VDC
- N2 serial communications; up to 6 annunciator modules per system
- Wiring: 18–14 AWG terminal blocks
- Four input types: unsupervised, supervised open, supervised open/short, H.O.A.
- UL 864, ULC, CSFM Listed; FM Approved; MEA (NYC) accepted
Compatible Panels
Simplex 4010
Life Safety Consultants has supplied genuine Simplex parts since 2002. For orders or technical assistance with the 4605-7401, call 1-888-557-0558 or email sales@lifesafetycom.com.
Additional information
| Weight | 1 lbs |
|---|---|
| Dimensions | 3 × 3 × 3 in |
| Condition | New |
| Part Type | Control Parts |
| Manufacturers | Simplex |
| Compatible Panels | Simplex 4010 |
| Cross Reference | 565-802 |
| Points | 24 selectable I/O |
| Output | 24 V / 75 mA each, 1.8 A total max at 32 VDC |
| Input voltage | 18-32 VDC |
| Current | 60 mA at 24 VDC |
| Wiring | 18-14 AWG |
| Comms | N2 serial |
| Listings | UL 864 / ULC / CSFM / FM / MEA |