The Edwards BPS10A is a 10-amp remote booster power supply. It adds 24 VDC filtered-regulated power and notification appliance circuits (NACs) to an existing fire alarm system.
The BPS10A is used when the host panel runs out of NAC current. As a result, large buildings can expand notification coverage without replacing the main panel. In addition, the booster supports auxiliary 24 VDC loads such as door holders and access control devices.
Capacity of the Edwards BPS10A
Total output is 10 amperes at 24 VDC. Each of the four NAC circuits is rated at 3 A maximum. Therefore, the booster handles four loaded circuits up to the 10 A combined ceiling.
Key Features
- Four Class B NAC outputs, field-convertible to two Class A circuits
- 3 A max per circuit, 10 A total across all NACs
- Independent 200 mA 24 VDC auxiliary output
- Signal rate options: continuous, 3-3-3 temporal, or follow-panel
- California rate available on BPS10CAA variant
- Synchronizes Edwards Genesis and Enhanced Integrity notification appliances
- Onboard charger for two internal sealed lead-acid batteries (up to 10 Ah each)
- Seven onboard diagnostic LEDs: per-NAC fault, battery, ground fault, AC
- Self-restoring overcurrent protection
- Separate trouble relay and AC fail contact
- Lockable EDWARDS steel cabinet with removable door
- Mounting brackets for up to three Signature Series modules
Compatible Panels
The BPS10A activation inputs accept any 6-45 VDC filtered-regulated source, or 11-33 VDC full-wave rectified. As a result, it works with EST3, EST3X, iO64, iO500, iO1000, FireShield Plus, and other Edwards panels that can drive a NAC. It is also driven directly by Signature Series control modules.
Specifications
- AC input: 120 VAC, 50/60 Hz, 580 W (BPS10A/230 is the 220-240 VAC model)
- Output voltage: 24 VDC, filtered and regulated
- Maximum total output: 10 A
- Maximum per NAC: 3 A
- Input current from existing NAC: 3 mA @ 12 VDC, 6 mA @ 24 VDC
- Internal supervisory current: 70 mA (+ 35 mA per AUX circuit)
- Internal alarm current: 270 mA
- Terminal wire size: 18 to 12 AWG
- Dimensions: 17″ H x 13″ W x 3.5″ D (43.2 x 33.0 x 8.9 cm)
- Shipping weight: 13 lb (5.9 kg)
- Operating temperature: 32°F to 120°F (0°C to 49°C)
- Humidity: 0 to 93% non-condensing
- NAC wiring: Class A or Class B
Agency Listings
UL 864 9th Edition (UOXX, Fire Alarm Systems). In addition: UL 636, UL 609, UL 294 (Access Control), UL 365, UL 1076, UL 1610 (Central Station), ULC-S527 (Canada), ULC-S303, C22.2 No. 205, and CSFM listed.
Order or Get Application Help
Life Safety Consultants has supplied Edwards / EST power supplies since 2002. To order the BPS10A or to size battery backup for your system, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 10 lbs |
|---|---|
| Dimensions | 17 × 8 × 5 in |
| Condition | New |
| Part Type | Power Extender Panel, Remote Power Supply |
| Manufacturers | Edwards |
| Compatible Panels | EST3,iO64,iO500 |
| Cross Reference | BPS6A |
| Output | 24VDC, NAC Current: 10A, Mounting: Remote/wall-mount |