The Edwards SIGA-CRR Polarity Reversal Relay Module is a Signature Series intelligent addressable output module. Specifically, its 24 VDC output reverses polarity on command from the loop controller. As a result, this drives a group of SIGA-AB4G Audible Sounder Bases on the data loop.
Importantly, the “polarity reversal” in this module’s name refers to the audible-base power circuit. Therefore, it is not a city-tie or municipal reverse-polarity reporting module. Instead, technicians use it strictly within Signature Series notification design.
Loop function
- Signature Series output module with factory-set Personality Code 8.
- Uses one module address on the SLC.
- LEDs: green flashes when polled; red illuminates when active.
Verified electrical specs
- Operating voltage: 15.2 to 19.95 VDC (19 VDC nominal) supplied by the loop controller.
- Standby current: 100 µA.
- Activated current: 100 µA.
- Relay: Form “C” dry contact.
- Contact rating: 2 A @ 24 VDC (pilot duty), 0.5 A @ 120 VAC.
Mounting
The SIGA-CRR mounts to a North American 2 1/2″ deep 1-gang box. Alternatively, install it in a 1 1/2″ deep 4″ square box with a 1-gang cover plus the SIGA-MP plate adapter.
- Construction: high-impact engineering polymer.
- Operating temperature: 32 to 120 °F.
- Humidity: 0 to 93% RH, non-condensing.
- Ship weight: 0.4 lb.
Panel compatibility
The SIGA-CRR works with Edwards Signature Loop Controllers in the EST3, EST3X, iO Series, and EST4 panel families.
Agency listings
Per the datasheet, the module is UL, ULC, CSFM, and MEA listed for fire alarm service.
Authoritative source: Edwards data sheet 85001-0239 Issue 7, SIGA-CRR Polarity Reversal Relay Module.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 1 lbs |
|---|---|
| Dimensions | 5 × 5 × 2 in |
| Condition | New |
| Manufacturers | Edwards |
| Part Type | Smoke Detector |