Altronix (FIRESWITCH108) 10a managed nac extender

$934.68

SKU: FIRESWITCH108 Brand:

2 in stock

The Altronix FireSwitch108 is a UL 864-listed managed NAC power extender with LCD and Ethernet management. Specifically, it provides eight programmable 24VDC notification appliance circuits, configurable as Class B NACs, Class A NACs, or auxiliary power outputs.

First, the FireSwitch108 accepts two Class A or two Class B trigger inputs from any 12 or 24VDC fire alarm control panel. Then, on-board logic drives eight programmable indicating circuits at up to 2.5 A per output. In addition, an integrated LCD plus Ethernet port enable local and remote status monitoring through the Altronix LINQ dashboard. As a result, integrators can program EOL resistor values per output and diagnose signal-circuit faults without opening the cabinet.

Altronix FireSwitch108 — Verified Specifications

  • Input: 120VAC, 60Hz, 4.8 A
  • FACP inputs: two (2) Class A or two (2) Class B (polarity reversal or dry contact); 12 or 24VDC compatible
  • Output configuration: eight (8) Class B, four (4) Class A, or any mix including aux power
  • Output rating: 24VDC regulated, power-limited; 2.5 A per output
  • Total alarm current: 10 A max; 7 A max standby without battery; 1 A with battery backup including aux (0.45 A Canadian)
  • Auxiliary: one (1) 1 A regulated battery-backed output
  • Operating modes: Temporal Code 3, Steady, Input-to-Output Follower, CO Temporal Code 4 (NFPA 720) for Gentex, Potter, System Sensor
  • Synchronization: up to twelve (12) FireSwitch108 units
  • Battery: two (2) 12VDC/12 AH sealed lead-acid or gel (sold separately)
  • Low DC Power Shutdown at 24VDC 70–75% to prevent deep discharge
  • Supervision: AC fail, battery fail, battery presence, signal-circuit trouble memory
  • Enclosure: 15.5″ x 12″ x 4.5″ steel; product weight 12.4 lb
  • BTU/Hr: 123

Verified Agency Listings

Furthermore, the FireSwitch108 is UL Listed (U.S. and Canada) under UL 864 (Control Units and Accessories for Fire Systems) and CAN/ULC-S527-99 (Control Units for Fire Alarm Systems). Also, it carries FM Approval and CSFM Approval, and complies with NFPA 72 and NFPA 720.

LCD + Ethernet Management

However, what sets the FireSwitch108 apart is the LINQ network interface. Specifically, the LCD identifies which output has a fault, while the Ethernet port allows remote programming and monitoring. Therefore, large installations can centralize NAC visibility across many cabinets without truck rolls for routine status checks.

Order or Discuss a Networked Rollout

To order the Altronix FireSwitch108 or plan a networked NAC rollout, call 1-888-557-0558. Also, you can email sales@lifesafetycom.com.

For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com

Additional information

Weight 13 lbs
Dimensions 6 × 16.5 × 13.5 in
Condition

New

Manufacturers

Life Safety

Part Type

Module