The Notifier NMM-100P is a miniature, intelligent addressable monitor module. It is the compact version of the NMM-100. First, it monitors one zone of normally-open, dry-contact initiating devices. As a result, conventional contacts gain a supervised address on the panel.
Because of its small size, the NMM-100P fits inside a device backbox. In addition, it connects with wire pigtails instead of terminal screws. Therefore, it suits tight installations where a full-size module will not fit.
Notifier NMM-100P wiring and supervision
The NMM-100P uses Style B (Class B) wiring only. Also, it excludes the status LED found on the NMM-100. A 47K end-of-line resistor supervises the monitored circuit. As a result, the panel still detects open or fault conditions on the zone.
This module connects to the Notifier FireWarden Series signaling line circuit (SLC). Furthermore, it communicates using the FlashScan and CLIP protocols.
Verified details
- Type: miniature addressable monitor module, one input zone
- Input: normally-open, dry-contact initiating devices
- Wiring: Style B (Class B) only; connects via wire pigtails
- Supervision: 47K end-of-line resistor (included)
- Mounting: fits inside a device backbox
- Note: excludes the LED and the Style D option of the NMM-100
- Compatibility: Notifier FireWarden Series addressable panels (FlashScan/CLIP)
Finally, the NMM-100P brings a single contact device into an addressable system. Therefore, it saves space without losing supervision.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.1 lbs |
|---|---|
| Dimensions | 4.5 × 1.5 × 1.5 in |
| Condition | New |
| Manufacturers | Notifier |
| Part Type | Pull Station |