A plug-in, ionization detector designed for two wire system operation

2 in stock

The Siemens DI-3 is a conventional two-wire ionization smoke detector. It is part of the Cerberus Pyrotronics System 3 family of plug-in smoke detection devices.

The DI-3 uses a dual-chamber ionization design. One chamber senses combustion products. The other serves as a reference. As a result, the detector compensates for temperature, humidity, and pressure changes that would otherwise shift sensitivity.

Sensitivity is preset at the factory but can be field-adjusted. In addition, it can be measured without removing the detector from its base. Sensitivity testing uses the Siemens TM-I3 test module through a front-accessible test jack.

Key Features of the Siemens DI-3

  • Self-compensating dual ionization chamber design
  • Conventional two-wire operation — not addressable
  • Adjustable sensitivity, with electrical-value sensitivity testing
  • Twist/lock mounting to the DB-3S low-profile base or ADB-3 audible base
  • Front-accessible sensitivity test jack and adjustment screw
  • Front-mounted alarm LED — locks in on alarm until panel reset
  • Air velocity rating: 0 to 300 ft/min (open-area applications)
  • Up to 30 detectors per Cerberus Pyrotronics conventional zone circuit
  • UL 268 and UL 268A listed; ULC, FM, CSFM, NY MEA approved

Compatible Systems and Bases

The DI-3 is designed for Cerberus Pyrotronics System 3 conventional zone modules. Specifically, it mounts to the DB-3S surface base on a 4″ octagonal, single-gang, or 4″ square wiring box. Alternatively, it mounts to the ADB-3 audible base on a 4″ square deep wiring box.

For high-altitude applications (3,000-8,000 ft), order the DI-3H variant. For intrinsically safe applications, order the DI-3IS with a CZM-1 zone module on an MXL panel.

Specifications

  • Sensing technology: Ionization, dual chamber
  • Operating voltage: 21 ± 3 VDC
  • Standby current: 100 µA (350 µA peak surge at power-up)
  • Alarm current: 80 mA
  • Operating temperature: 32°F to 100°F (0°C to 38°C) per UL
  • Humidity: 0 to 93% RH
  • Air velocity rating: 0 to 300 ft/min
  • Compatible base: DB-3S (standard) or ADB-3 (audible)
  • Cross-reference Siemens catalog number: 500-081806
  • Shipping weight: 1 lb (0.45 kg)

Availability and Replacement Option

The Siemens DI-3 has been discontinued by the manufacturer. As an alternative, consider the Siemens OP121 photoelectric detector with the DB-11 base. The OP121 keeps your Siemens system in service. In addition, photoelectric technology better suits most modern installations.

Order or Get Application Help

Life Safety Consultants stocks Siemens Cerberus Pyrotronics legacy parts when available. To check current stock on the Siemens DI-3 or to plan an upgrade to the OP121, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.

For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com

Additional information

Weight .5 lbs
Dimensions 6.5 × 6.5 × 2.5 in
Condition

New

Part Type

Base, Detector Base, Smoke Detector

Manufacturers

Siemens

Compatible Panels

MXL, MXLV, FireFinder XLS, Sinteso

Compatible Bases

DB-11

Cross Reference

500-081450

Detection

Ionization, Protocol: Siemens CLIP addressable, Part #: 500-081450, Base: DB-11 (sold separately)