The Simplex 4099-9006 is an addressable dual-action manual pull station. It uses the familiar Simplex pull-station housing with an integral addressable communication module (IAM).
Dual action means two deliberate motions are required. First, push the spring-loaded interference plate marked PUSH. Then, pull the handle down firmly. As a result, the station breaks an internal plastic rod and signals alarm. This two-step design helps deter accidental and vandal-triggered alarms.
The integral IAM constantly reports station status to the fire alarm control panel. Communications run over IDNet or MAPNET II wiring. In addition, an LED on the front flashes during normal communications. The LED goes steady on when the station is activated.
Key Features of the Simplex 4099-9006
- Dual-action push-then-pull activation deters nuisance alarms
- Integral individually addressable module — single device address per station
- Operates on IDNet or MAPNET II addressable SLC wiring
- LED indicator: flashing for normal comms, steady on for active alarm
- Replaceable plastic break rod — reset by replacing the rod, not the station
- Eight-position DIP switch for address setting under a resealable label
- UL Listed to Standard 38 (manual fire alarm boxes)
- ADA-compliant when installed at the height specified by NFPA 72
Compatible Panels
The 4099-9006 operates on either IDNet or MAPNET II SLCs. IDNet panels include Simplex 4007ES, 4010, 4010ES, 4100ES, and 4100U. MAPNET II support covers 4100, 4120, and 4020 panels.
Installation Details
- Mounts in a single-gang or 4″ square electrical box (supplied separately)
- IDNet channel supports address codes 1-250
- MAPNET II channel supports address codes 1-127
- SLC wire: 18 AWG twisted pair, shielded recommended
- Maximum run: 2,500 ft from panel to farthest device
- Maximum total wiring (including T-taps): 10,000 ft
- Installation instructions: Simplex 579-1135
- Replaces the legacy Simplex 4099-9003
Order or Get Application Help
Life Safety Consultants has supplied genuine Simplex pull stations since 2002. To order the Simplex 4099-9006 or to confirm panel and address compatibility, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | .25 lbs |
|---|---|
| Dimensions | 5 × 5 × 5 in |
| Condition | New |
| Part Type | Dual Action, Manual, Pull Station |
| Manufacturers | Simplex |
| Compatible Panels | Simplex 4007ES, 4008, 4010, 4010ES, 4100ES, 4100U, 4020, 4100, 4120, Simplex 2120 CDTs with MAPNET II |
| Cross Reference | 06501211,4099-9003 |
| Specification | IDNet/MAPNET II addressable, dual-action push-then-pull, integral IAM, LED indicator, UL Listed Std 38, ADA compliant, includes 2099-9804 break-rod |









