The Edwards 270-SPO pull station is a single-action, break-glass manual initiating device. First, a user breaks the glass rod. Then, the station latches in alarm until reset with the key. As a result, accidental activation is unlikely in normal traffic areas.
Specifically, the “SPO” designation means Single Pole, Open. Therefore, the alarm contact is normally open and closes on activation. In addition, screw terminals make field wiring straightforward for the installing technician.
Edwards 270-SPO pull station construction
The 270 series uses a die-cast metal body painted red with silver stripes. Furthermore, the rugged casting holds up in schools, offices, and industrial corridors. Also, either flush or surface mounting is supported. For flush installs, use a standard 4-inch North American square box with a single-gang plaster cover.
Verified specifications
- Operation: single action, break glass, key reset
- Contact configuration: single pole, normally open (SPO)
- Contact rating: 3 A at 30 VAC / 60 VDC
- Wiring: screw terminals
- Body: die-cast metal, red with silver stripes
- Operating temperature: 32 to 120°F (0 to 49°C)
- Mounting: flush or surface (4-inch square box for flush)
- Listings: UL 38, CSFM, FM Approved, MEA Listed
For new installs or one-for-one replacements, the 270-SPO drops into conventional fire alarm circuits. However, always confirm panel-specific supervision and EOL resistor values before commissioning.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.9 lbs |
|---|---|
| Dimensions | 4 × 5 × 3.5 in |
| Condition | New |
| Manufacturers | Edwards |
| Part Type | Pull Station |