The Edwards EBPS6A is a 6.5 amp Remote Booster Power Supply for fire alarm Notification Appliance Circuits. First, it expands the NAC capacity of an existing fire alarm control panel. As a result, you can power more horns, strobes, and speakers from a single system.
Edwards EBPS6A architecture
The unit ships with four independent Class B NACs that convert to two Class A circuits via jumper. Each circuit handles up to 3.0 A. In addition, the four NACs share a 6.5 A total budget. Furthermore, NACs 1 through 4 can be reconfigured as auxiliary 24 Vdc outputs. Also, a dedicated 200 mA auxiliary output is included for accessory power.
Signal coordination and synchronization
The EBPS6A generates three signal rates internally. First, continuous tone for steady horns. Then, the 3-3-3 temporal pattern required by NFPA 72 for fire evacuation. Alternatively, the booster can follow the host panel’s NAC signal rate. As a result, it provides Genesis strobe and horn synchronization without a separate sync module.
Verified specifications
- AC input: 120 V AC, 50/60 Hz, 250 W
- NAC output: 3.0 A max per circuit, 6.5 A total across all NACs at 24 V DC nominal
- NAC wiring: Class A or Class B (jumper-configurable)
- Auxiliary output: 200 mA dedicated, plus optional NAC-as-AUX conversion
- Sensing input: 3 mA at 12 V DC / 6 mA at 24 V DC (from existing NAC)
- Trouble relay: 2 A at 30 V DC, with 16-second AC-fail delay
- Battery compartment: up to 10 Ah in cabinet (2 x 12V10A); 24 Ah max with external box
- Wire gauge: 18 to 12 AWG terminals
- Operating environment: 32 to 120 F (0 to 49 C), 0 to 93% RH non-condensing
- Cabinet: 17″ x 13″ x 3.5″ wall-mount steel, 3/4″ knockouts
Status indication and supervision
Seven on-board LEDs report system health. Specifically, one LED per NAC, plus battery, ground fault, and AC power indicators. As a result, troubleshooting is fast without test gear. Furthermore, fault conditions detected by the EBPS open the host panel’s NAC for centralized annunciation.
Agency listings
UL 864 (Control Units and Accessories for Fire Alarm Systems), ULC, and CSFM. The Edwards EBPS6A is intended for fire-alarm and mass-notification applications.
Related products
For higher capacity, see the EBPS10A (10 A version). In addition, the BPSEQ seismic kit secures internal batteries for high-seismic installations. For 220-240 V markets, see EBPS6A/230.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 14.5 lbs |
|---|---|
| Dimensions | 18 × 14.5 × 5 in |
| Condition | New |
| Manufacturers | Edwards |
| Part Type | Replacement Part |