The Edwards SIGA-CT2 is an intelligent, addressable Dual Input Module from the Edwards Signature Series. Specifically, it connects two independent Class B normally-open dry contact initiating device circuits to the Signature SLC. As a result, two conventional inputs can report individually through a single physical module.
Each of the two circuits has its own address on the loop. Therefore, the panel sees them as separate devices, with separate point IDs in the event log.
How the SIGA-CT2 Works
First, each connected device closes its dry contact when triggered. Then, the SIGA-CT2’s microprocessor evaluates each input and reports it independently to the Signature loop controller. In addition, the two circuits can use the SAME personality code or DIFFERENT personality codes. As a result, one module can serve, for example, a waterflow alarm on circuit A and a tamper switch on circuit B.
Personality Codes — Four Configurable Behaviors per Circuit
- Code 1 — Alarm, Latching: Pull stations, heat detectors, similar normally-open initiating devices.
- Code 2 — Alarm, Delayed Latching (~16 sec): Waterflow alarm switches that require a retard.
- Code 3 — Active, Non-Latching: Monitor inputs from fans, dampers, doors.
- Code 4 — Active, Latching: Supervisory and tamper switches that hold state until reset.
Codes 1, 2, 3, and 4 can be MIXED across the SIGA-CT2’s two circuits. Therefore, a single module can carry two unrelated functions.
Common Applications
- Two waterflow switches on a single sprinkler riser zone
- One waterflow switch and one matching tamper switch on the same control valve
- Pairs of monitor inputs for fans, dampers, or smoke control devices
- Two pull stations or two supervisory switches in a small area
- Bringing conventional dry-contact devices onto a Signature SLC during a retrofit
Key Features
- Two independent Class B normally-open dry contact inputs
- Uses 2 addresses on the Signature SLC (one per circuit)
- Per-circuit selectable personality codes (alarm, delayed alarm, active, supervisory)
- Electronic addressing — no DIP switches or rotary dials
- Automatic device mapping on the Signature loop
- Stand-alone operation if loop polling pauses
- Non-volatile memory stores serial number, device type, and job number
- Ground fault detection per address
- Green LED for polling, red LED for alarm/active
- Mounts in a standard North American 1-gang or 4″ square electrical box
- UL, ULC, MEA, and CSFM listed
Specifications
- Module type: Dual input, Class B, normally-open contacts
- Type code: 49 (factory set)
- Address use: 2 module addresses (one per input circuit)
- Operating voltage: 15.2 to 19.95 Vdc (19 Vdc nominal)
- Operating current: 396 µA standby / 680 µA active
- Operating temperature: 32°F to 120°F (0°C to 49°C)
- Humidity: 0 to 93% RH, non-condensing
- Wire range: #12 to #18 AWG
- IDC wire limits: 50 Ω total per circuit (25 Ω per wire); 0.1 µF capacitance per circuit
- Maximum IDC distance: 4,000 ft (1,219 m) to EOL resistor
- EOL resistor: 47 KΩ per circuit
- Weight: 0.4 lb (0.15 kg)
- Datasheet: Edwards / GE Security 85001-0241
Compatibility
The SIGA-CT2 communicates only with the Edwards Signature Loop Controller. Therefore, it works with Signature-equipped Edwards panels such as the EST3, EST3X, iO Series, and QuickStart-ES. Always confirm panel compatibility against the firmware revision in your system.
Important Application Note
The SIGA-CT2 will not support 2-wire smoke detectors. Specifically, it is designed only for dry-contact initiating devices and monitor inputs. For 2-wire smoke detection, use the appropriate Signature 2-wire smoke detector interface instead.
SIGA-CT2 vs. SIGA-CT1
If you only need ONE input circuit, the SIGA-CT1 is the lower-cost choice and uses just one address on the loop. The SIGA-CT2 is the right pick when two unrelated inputs sit close together and you can save mounting hardware and panel labels by combining them.
Order the SIGA-CT2
Life Safety Consultants stocks the SIGA-CT2 along with the full Signature Series module family. To confirm the right personality codes for your application or place an order, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.5 lbs |
|---|---|
| Dimensions | 2 × 2 × 2 in |
| Manufacturers | Edwards |
| Compatible Panels | EST3,EST3X,iO64,iO500,QuickStart QS1 |
| Cross Reference | SIGA-CT1,SIGA-CC1 |
| Input | 2 x supervised contacts on 1 SLC address |
| Protocol | Edwards Signature SLC |
| Address | Single point (dual input) |
| Supervision | Open and short per input |
| Mounting | Standard electrical box or Signature enclosure |