The Silent Knight SD500-LIM line isolator module protects the SLC loop on Silent Knight addressable panels. It acts as an automatic switch that opens when a wiring fault shorts the loop. As a result, only the shorted segment drops out — every other device keeps operating.
The panel still sees the event. Specifically, the fault reports as a trouble condition while protected devices stay online. The module works on Style 7 (Class A) and Style 4 (Class B) SLC wiring. In addition, a loop supports up to 127 isolator devices (SD500-LIM or SD505-6IB).
Silent Knight SD500-LIM Specifications
- Operating voltage: 32 VDC
- Battery current draw during AC loss: 92 µA alarm/standby; SLC current: 50 µA
- Maximum SLC loop resistance: 50 Ω (0–50 devices, up to 10 Ω per branch)
- Operating temperature: 32°F to 120°F (0°C to 49°C); indoor use only
- Dimensions: 4-7/8″ x 4-7/8″ x 7/8″
- Mounts in a standard dual-gang electrical switch box
- All wiring is supervised and power-limited
Install isolators at segment boundaries you want protected. Then a short at any point only isolates the devices between isolators.
Order the Silent Knight SD500-LIM
Life Safety Consultants stocks genuine Silent Knight replacement parts. To order the SD500-LIM or check compatibility, call 1-888-557-0558. You can also email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.5 lbs |
|---|---|
| Dimensions | 0.5 × 8 × 6 in |
| Condition | New |
| Manufacturers | Silent Knight |
| Part Type | Module |