The Simplex 4090-9008 is a Dual Contact Relay Individual Addressable Module (IAM). It gives the fire alarm panel control of two Form C dry contacts using a single device address.
Typical uses include elevator capture, HVAC shutdown, pressurization fan control, and damper actuation. In addition, both contact states are reported back to the panel. Therefore, the panel can verify that each controlled function fired.
The 4090-9008 is a low-power latching design. As a result, IDNet or MAPNET II wiring supplies both data and module power. No separate 24 VDC feed is required. On initial power-up — or on loss of communications — both relays default to OFF.
Key Features of the Simplex 4090-9008
- Two independent Form C (DPDT) dry contacts on a single addressable point
- Each common is fused with a 2 A fast-acting fuse
- Power-limited rating: 2 A @ 30 VDC resistive, 1 A @ 30 VDC inductive
- Not rated for incandescent switching
- Visible LED flashes on communications; can be set at the panel to indicate active state
- Compact sealed housing for indoor commercial use
- Mounts in a standard 4″ square electrical box (2 1/8″ minimum depth)
- Optional 4090-9813 adapter plate for 4 11/16″ boxes
- UL Listed; California State Fire Marshal listed (CSFM 7300-0026:0311)
Compatible Panels
For IDNet wiring, the 4090-9008 works with Simplex 4100ES, 4010ES, and 4100U panels. For MAPNET II, it works with 4100, 4100U, 4100ES, 4120, 4020, and 2120 CDT transponders. IDNet operation requires panel firmware 3.12.04 or higher.
Specifications
- Communications: IDNet or MAPNET II, 1 address per device
- Power: supplied entirely by communications wiring
- Wire connections: screw terminals, #18 to #14 AWG
- Wiring distance: up to 2,500 ft from panel; 10,000 ft total including T-taps
- Dimensions: 4 1/8″ H x 4″ W x 1 3/8″ D (105 x 102 x 35 mm)
- Operating temperature: 32°F to 120°F (0°C to 49°C)
- Humidity: up to 93% RH at 100°F (38°C), indoor use
- Installation instructions: Simplex 579-1040
Order or Get Application Help
Life Safety Consultants has supplied genuine Simplex addressable modules since 2002. To order the Simplex 4090-9008 or to confirm panel compatibility, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 1 lbs |
|---|---|
| Dimensions | 5 × 5 × 2 in |
| Condition | New |
| Manufacturers | Simplex |
| Compatible Panels | 4100ES, 4020, 4010, 4008 |
| Protocol | IDNet/MAPNET II, Inputs: 2x normally open dry contact, Output: Relay, Addressing: Independent or combined per input |