The Simplex 4009-9201 IDNet NAC Extender adds supervised notification appliance circuit capacity to Simplex 4010 and 4100U fire alarm control panels where the base panel NAC power is insufficient — a common scenario in ADA compliance upgrades and large occupancy expansions. The 4009-9201 draws 120VAC input (3A @ 102–132 VAC, 60 Hz) and delivers up to 8A total output across four standard Class B (Style Y) NACs rated at 2A each @ 24 VDC nominal. The internal power supply doubles as a battery charger, supporting internal batteries up to 12.7 Ah or external 18 Ah batteries. Input control is via IDNet addressable communications — one address per extender — or from conventional 24 VDC NAC inputs. Up to 5 units can be connected per IDNet channel.
Key Features
- Input voltage: 120VAC, 3A @ 102–132 VAC, 60 Hz
- Standard NAC outputs: 4 × Class B (Style Y), rated 2A each @ 24 VDC
- Optional expansion: +4 NACs via 4009-9807 module, rated 1.5A each (8 NAC total)
- Total output capacity: 8A maximum across all NACs and auxiliary loads
- Auxiliary output: 500 mA @ 24 VDC nominal
- Battery charger: internal batteries up to 12.7 Ah; external cabinet for 18 Ah
- IDNet input: single address, supports device-level earth fault location
- Conventional NAC input option: reverse polarity, 3 mA @ 24 VDC alarm, 18–32 VDC
- IDNet max distance from source: 2,500 ft (762 m)
- IDNet output: up to 100 devices, 2,500 ft to farthest device
- Up to 5 × 4009-9201 units per IDNet channel
- SmartSync two-wire control compatible
- WALKTEST operation supported
- Operating temp: 32° to 120°F (0° to 49°C); Humidity: 10–90% RH
- Wiring: terminal blocks, 18 AWG stranded to 12 AWG solid
- UL Listed Standard 864; ULC listed as 4009-9202CA; CSFM; FM; MEA (NYC)
Compatible Panels
- Simplex 4100U (requires revision 11 software or higher)
- Simplex 4010 (requires revision 2 software or higher)
- Also accepts conventional 24 VDC NAC input from other panels
Optional Modules
- 4009-9807 — Additional 4-point NAC module (1.5A/NAC)
- 4009-9808 — IDNet Communications Repeater, Class B (Style 4)
- 4009-9809 — IDNet Communications Repeater, Class A (Style 6)
- 4009-9810 — Fiber Optic Receiver/Repeater, Class B
- 4009-9811 — Fiber Optic Receiver/Repeater, Class A
- 4009-9805 — Class A (Style Z) Two-Circuit Adapter Module
Life Safety Consultants stocks 10 units of the 4009-9201 ready to ship. The 4009 IDNet NAC Extender is one of the most requested expansion modules for 4100U and 4010 systems. Call 1-888-557-0558 or email sales@lifesafetycom.com.
Additional information
| Weight | 22.9 lbs |
|---|---|
| Dimensions | 20.4 × 17.1 × 7.8 in |
| Condition | New |
| Part Type | NAC Panel, Power Extender Panel |
| Manufacturers | Simplex |
| Compatible Panels | Simplex 4100U (rev. 11+), Simplex 4010 (rev. 2+), also accepts conventional 24 VDC NAC input |
| Cross Reference | 4009-9201, 4009-9202CA (ULC) |
| Specification | 120VAC input, 3A @ 102-132 VAC 60Hz, 4 Class B NACs @ 2A each, 8A total max, 500mA aux, Battery charger 12.7Ah internal / 18Ah external, SmartSync, WALKTEST, 18-12 AWG, UL 864 |