The Edwards SIGA-SB is the standard mounting base for Edwards Signature Series intelligent detectors. Specifically, it connects the detector head to the signaling line circuit (SLC). In addition, it carries wiring terminals for an optional remote alarm LED (SIGA-LED).
This base ships in white, high-impact engineering polymer. As a result, it fits in clean with most ceiling finishes and is durable enough for commercial and institutional use.
How the Edwards SIGA-SB Connects to Your System
First, the SIGA-SB mounts to a compatible electrical box on the ceiling or wall. Then, the technician wires the SLC IN and SLC OUT terminals — each wire is broken at the terminal, not looped. As a result, the system supervises every wire run end-to-end.
Next, a Signature Series detector head plugs into the base by aligning and twisting clockwise. The address label goes on the inside rim of the base. Furthermore, an optional SIGA-TS trim skirt covers the surrounding box for a finished appearance.
Compatible Signature Series Detectors
The SIGA-SB accepts the full range of standard Signature Series detector heads, including:
- SIGA-PS / SIGA2-PS — Photoelectric smoke detectors
- SIGA-PD — Photoelectric duct-style smoke detectors
- SIGA-PHS — Photoelectric and heat combination
- SIGA-IPHS — Intelligent photoelectric/heat sensor
- SIGA-IS — Ionization smoke detector
- SIGA-HFS — Heat detector (fixed temperature)
- SIGA-HRS — Heat detector (rate of rise)
For relay or isolator base functions, see the SIGA-RB (relay base) or SIGA-IB (isolator base) instead.
Compatible Electrical Boxes
- North American single-gang box
- 3-1/2″ × 1-1/2″ deep octagon box
- 4″ × 1-1/2″ deep octagon box
- European single-gang box (75 mm with 60.3 mm fixing centers)
- BESA box with 60.3 mm fixing centers
Key Features
- Standard mounting base for all Signature Series Edwards detectors
- SLC IN / SLC OUT wiring terminals for supervised loop operation
- Terminals for optional SIGA-LED remote alarm indicator
- White high-impact engineering polymer housing
- Fits a wide range of North American and European back boxes
- SIGA-TS trim skirt accessory available for finished appearance
- Address label area built into the base for clear field identification
- Room-side accessible wiring terminals for clean maintenance access
Specifications
- Base type: Standard (non-isolator, non-relay) detector mounting base
- Compatible system: Edwards Signature Series SLC
- Wire size: 12 to 18 AWG (1.0 to 4.0 mm²) — 16 to 18 AWG preferred
- Mounting screw torque: 18 lbf-in (2.0 N·m) max
- Terminal screw torque: 12 lbf-in (1.4 N·m) max
- Maximum SIGA-LED wire resistance: 10 Ω per wire
- Housing material: High-impact engineering polymer, white
- Operating temperature: 32°F to 120°F (0°C to 49°C)
- Humidity: 0 to 93% RH, non-condensing
- Standards: CAN/ULC-S529-09, UL 268, UL 521
- Installation sheet: Edwards P/N 387019P-EN, Rev 11
Compatible Panels
Detectors mounted on the SIGA-SB communicate over the Edwards Signature Loop Controller. Therefore, the base works with Signature-equipped Edwards panels such as the EST3, EST3X, iO Series, and QuickStart-ES. Always confirm panel compatibility against the firmware revision in your system.
Order the Edwards SIGA-SB
Life Safety Consultants stocks the Edwards SIGA-SB along with the full Signature Series detector and base lineup. To order or to confirm compatibility for your detector head, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.25 lbs |
|---|---|
| Dimensions | 5 × 5 × 1 in |
| Condition | New |
| Part Type | Base, Detector Base, Mount, Smoke Detector |
| Manufacturers | Edwards |
| Compatible Panels | EST3,EST3X,iO64,iO500,QuickStart QS1 |
| Compatible Bases | SIGA-PS,SIGA-PD,SIGA-IPHS,SIGA-PHD |
| Cross Reference | SIGA-IB,SIGA-SB4 |
| Platform | Signature Series SLC |
| Footprint | 4-inch standard |
| Type | Detector mounting base |
| Addressable | Yes |