The Simplex 4605-7401 is a 24-point programmable input/output module. It also carries the board number 565-802. First, it installs in the Simplex 4010 addressable fire alarm control panel. As a result, it expands the panel’s input and output capacity.
How the Simplex 4605-7401 works
Each of the 24 points is individually selectable. Therefore, you can set any point as an input or an output. Four input types are supported. Specifically, these are unsupervised switch, supervised for open, supervised for open or short, and monitored three-position H.O.A.
Outputs are rated 24 V at 75 mA each. In addition, total output is capped at 1.8 A at 32 VDC. Also, each output is selectable for continuous on, slow flash, or fast flash.
Specifications
- 24 individually selectable I/O points per module
- Output rating: 24 V at 75 mA each; 1.8 A total max at 32 VDC
- Input supply voltage: 18 to 32 VDC
- Operating current: 60 mA at 24 VDC
- N2 serial communications; up to 6 annunciator modules per system
- Wiring: 18 to 14 AWG terminal blocks
- UL 864, ULC, CSFM Listed; FM Approved; MEA (NYC) accepted
Compatible panels
The 4605-7401 works with the Simplex 4010 panel. For orders or technical help, call our team. Also, Life Safety Consultants has supplied genuine Simplex parts since 2002.
For more information, contact the Life Safety Consultants team at 1-888-557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 1 lbs |
|---|---|
| Dimensions | 3 × 3 × 3 in |
| Condition | New |
| Part Type | Control Parts |
| Manufacturers | Simplex |
| Compatible Panels | Simplex 4010 |
| Cross Reference | 565-802 |
| Points | 24 selectable I/O |
| Output | 24 V / 75 mA each, 1.8 A total max at 32 VDC |
| Input voltage | 18-32 VDC |
| Current | 60 mA at 24 VDC |
| Wiring | 18-14 AWG |
| Comms | N2 serial |
| Listings | UL 864 / ULC / CSFM / FM / MEA |