Edwards (EOL-4K7L) Supervision resistor. use in crc with no locks being powered strike to maintain supervision.

$16.42

SKU: EOL-4K7L Brand:

Supervision Resistor. Use in CRC with no locks being powered strike to maintain supervision.

18 in stock

The Edwards EOL-4K7L is a 4.7K ohm supervision resistor for Controlled Releasing Circuits (CRC) and similar supervised auxiliary loops. First, it maintains line supervision on a CRC when no powered door strike or lock is connected. As a result, the panel reads “normal” instead of “open” on circuits that would otherwise be empty.

Why a CRC needs a 4.7K resistor

Edwards releasing and access-control modules supervise their output circuits with a small monitoring current. Then, that current must return through a known load. As a result, an unloaded CRC reads as a trouble condition. The EOL-4K7L provides exactly the 4.7K ohm return path the panel expects.

Where the Edwards EOL-4K7L is used

Install the EOL-4K7L at the FAR END of a supervised CRC where no electric strike or magnetic lock is wired. Specifically, this applies to spare CRC outputs, future-expansion runs, and partial installations where some doors are deferred. Furthermore, when a powered strike IS installed, the strike’s internal coil typically provides the supervisory return – check the panel manual for the specific load model.

Verified scope

  • Resistance: 4,700 ohm (4.7K, denoted “4K7” in Edwards SKU convention)
  • Form: resistor with pre-attached wire leads
  • Function: replacement supervisory load for unused Controlled Releasing Circuits and similar 4.7K-supervised auxiliary outputs
  • Installation location: at the far end of the supervised CRC, between the two conductors
  • Required by: NFPA 72 for supervised wiring; specific Edwards module installation manuals

What this product is, and is not

The EOL-4K7L is a passive electronic component. As a result, it carries no standalone UL listing. Instead, the listing flows from the parent module and panel. Therefore, do not substitute a different ohm value: the module will report a trouble.

Related products

For 10K ohm fire-alarm initiating circuits, see EOL-10. For 47K ohm circuits, see EOL-47KL. Also see the Edwards EOL47PK7 (4.7K bulk pack) for multi-circuit jobs. Cross-reference the panel manual.

For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com