Edwards G1R-C Genesis Chime — Red Wall-Mount Audible
The Edwards G1R-C is a red-finish Genesis Series chime. First, note that it produces an audible mellow tone only. It does not include a strobe.
This appliance is intended for private-mode audible signaling. As a result, Edwards specifies horns or horn-strobes (not chimes) for public-mode fire alarm evacuation tone.
Verified specifications
- Operating voltage: filtered 16-33 VDC or unfiltered 16-33 Vdc FWR
- Output: 60 strokes per minute (default); field-jumper for temporal pattern; coded with optional G1M Signal Master
- Audible output (high dB, 24 V, anechoic average): 67.8 dBA at 10 ft; peak 78.6 dBA. UL 464 reverberation value: 60.8 dBA
- Low dB jumper option drops output approximately 5 dB
- Typical current at 24 VDC: 44 mA high dB / 26 mA low dB
- Mounting: indoor wall mount only; 1-gang flush, surface (27193 box), or oversized openings with G1RT trim plate
- Operating environment: 32-120°F (0-49°C), 93% RH
- Wire size: #18 to #12 AWG
- Dimensions: 4-1/2″ H x 2-3/4″ W x 13/16″ D (113 x 68 x 21 mm)
Agency listings
Per K85001-0574, the Genesis chime family carries UL 464, CSFM, CE, FCC, and MEA listings. In addition, the strobe-equipped siblings carry UL 1971 and UL 1638 — those listings do not apply to the chime-only G1R-C.
Compatible synchronization sources
The G1R-C synchronizes with the G1M, G1M-RM, SIGA-CC1S, SIGA-MCC1S, BPS6A, and BPS10A. Specifically, coded chime operation requires a Genesis Signal Master.
Choosing the right Genesis variant
First, select G1R-C for red-finish indoor chime with no marking. Then, choose G1RF-C if a FIRE marking is required. For paired audible-plus-visual notification, use G1R-CVM (chime-strobe) or G1R-HDVM (horn-strobe) instead.
For more information, contact the Life Safety Consultants team at 1-888-557-0558, or email us at: sales@lifesafetycom.com.
Additional information
| Weight | 0.3 lbs |
|---|---|
| Dimensions | 5 × 3 × 2 in |
| Condition | New |
| Manufacturers | Edwards |
| Part Type | Strobe |