IDNet and MapNet II surface mount, control relay ZAM

The Simplex 2190-9163 is a surface-mount Control Relay Zone Addressable Module (ZAM). It gives a Simplex addressable fire alarm panel one DPDT relay output for auxiliary control.

Typical uses include elevator capture, HVAC shutdown, pressurization fan control, and damper actuation. In addition, the ZAM reports its relay state back to the panel. As a result, the panel can verify that the controlled function actually fired.

The 2190-9163 communicates over IDNet or MAPNET II addressable SLC wiring. Therefore, one device address controls the dry-contact output remotely from the fire alarm panel. Furthermore, both data and operating power come from the addressable channel — no separate 24 VDC feed is required.

Key Features of the Simplex 2190-9163

  • Dual Pole Double Throw (DPDT) relay output
  • Communicates on IDNet or MAPNET II addressable SLC
  • Single device address per module
  • Surface-mount cover for easy field installation
  • Power supplied entirely by addressable wiring
  • Genuine Simplex part — cross-references to 0617610
  • Replaces older ZAM revisions on legacy MAPNET II loops

Compatible Panels

The 2190-9163 works with Simplex 2120, 4008, 4010, 4010ES, 4020, 4100, 4100ES, and 4100U fire alarm panels. Specifically, it operates on the IDNet or MAPNET II SLC channels offered by these panels.

Typical Applications

  • Elevator capture — recall on alarm
  • HVAC shutdown — fan and air handler control
  • Stairwell pressurization fan activation
  • Smoke damper position control
  • Door release on alarm
  • Any auxiliary function needing a single addressable dry contact

Specifications

  • Module type: Control Relay ZAM, surface cover
  • Relay output: DPDT (2-pole, 2-throw) dry contact
  • Communications: IDNet or MAPNET II, 1 address per module
  • Supervisory current: 10 mA @ 24 VDC
  • Alarm current: 40 mA @ 24 VDC
  • Power: supplied entirely by SLC wiring
  • Simplex part number cross-reference: 0617610

Order or Get Application Help

Life Safety Consultants has supplied genuine Simplex addressable modules since 2002. To order the Simplex 2190-9163 or to confirm panel compatibility, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.

For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com

Additional information

Weight .25 lbs
Dimensions 5.5 × 5.5 × 2 in
Condition

New

Part Type

Zone Addressable Modules (ZAM)

Manufacturers

Simplex

Compatible Panels

2120, 4008, 4010, 4010ES, 4020, 4100, 4100ES, 4100U

Cross Reference

0617610

Type

Control relay ZAM, Relay output: DPDT, Protocol: IDNet and MAPNET II, Mount: Surface, Dimensions: 5.5 x 5.5 x 2 in, Weight: 0.25 lb, Condition: New

 

 

 

 

 

Description

  • MAPNET II zone adapter modules (ZAMs) provide an addressable interface between conventional zone devices and the host fire alarm control panel.
  • Monitor ZAMs provide status monitoring and supervision of an initiating device circuit (IDC) zone and are used for circuits with non-addressable detectors and for other contact closures such as waterflow and tamper switches or non-addressable manual stations. Different models of Monitor ZAMs are available for two-wire IDCs Class B, or Class A, and for four-wire IDCs with Class B IDC input. Each type required a separate 24 VDC input power from a listed fire alarm power supply.
  • Signal ZAMs supervise and operate 24 VDC notification appliances, speakers, and telephone circuits. Output capacity is up to 2 A @ 24 VDC, or 50 W of 25 VRMS speakers, or up to three simultaneously activated firefighter phones. The signal ZAM is available for either Style Y/Class B or Style Z/Class A operation for notification appliance circuits.

 

Features

  • MAPNET II ZAMs provide an addressable interface to conventional fire alarm zone circuit devices** including:
    • Initiating devices (Monitor ZAM)
    • Notification appliance circuits (Signal ZAM)
    • Control relays (Control ZAM)
  • These ZAMs are compatible with the following Simplex® fire alarm control panels when equipped with MAPNET II communications:
    • 4100/4100U Series fire alarm control panels
    • 4100 Series Universal Transponders
    • 4120 Series Network node fire alarm control panels
    • 4020 Series fire alarm control panels
    • 2120 Communicating Device Transponders
  • MAPNET II communications can be wired:
    • NFPA Style 4/Class B or Style 6/Class A
    • Style 4/Class B communications may be wired either “T” tapped or In/Out
  • Convenient DIP switch address selection
  • UL listed to Standard 864