The Edwards SIGA-CT1 is an intelligent, addressable Single Input Module. Specifically, it connects one Class B normally-open dry contact initiating device circuit to the Edwards Signature Series SLC. As a result, conventional contact-based devices can report through a single address on the addressable loop.
The module’s behavior is set by one of four personality codes. Therefore, the same hardware can act as an alarm input, a waterflow input, a monitor input, or a supervisory input.
How the Edwards SIGA-CT1 Works
First, the connected initiating device closes its dry contact. Then, the module’s on-board microprocessor evaluates the input and reports to the Signature loop controller. In addition, the module continues to function in stand-alone mode if loop polling stops temporarily — supporting the panel’s required fail-safe operation.
A 47K end-of-line resistor terminates the supervised initiating device circuit. Furthermore, the module uses electronic addressing — the loop controller (or the SIGA-PRO service tool) assigns the address. As a result, there are no DIP switches or rotary dials to set in the field.
Personality Codes — Four Configurable Behaviors
- Code 1 — Alarm, Latching: For pull stations, heat detectors, and similar Class B initiating devices.
- Code 2 — Alarm, Delayed Latching (~16 sec): For waterflow alarm switches that require a built-in retard.
- Code 3 — Active, Non-Latching: For monitor inputs from fans, dampers, doors, and similar devices.
- Code 4 — Active, Latching: For supervisory and tamper switches that should hold their state until reset.
Key Features
- One Class B normally-open dry contact IDC input
- Uses 1 address on the Signature SLC
- Selectable personality codes — alarm, delayed alarm, active monitor, supervisory
- Electronic addressing — no DIP switches or dials
- Automatic device mapping on the Signature loop
- Stand-alone operation if loop polling pauses
- Non-volatile memory stores serial number, device type, and job number
- Ground fault detection per address
- Green LED for polling, red LED for alarm/active
- Mounts in a standard North American 1-gang or 4″ square electrical box
- UL, ULC, MEA, and CSFM listed
Specifications
- Module type: Single input, Class B, normally-open contact
- Type code: 48 (factory set)
- Address use: 1 module address
- Operating voltage: 15.2 to 19.95 Vdc (19 Vdc nominal)
- Operating current: 250 µA standby / 400 µA active
- Operating temperature: 32°F to 120°F (0°C to 49°C)
- Humidity: 0 to 93% RH, non-condensing
- Wire range: #12 to #18 AWG
- IDC wire limits: 50 Ω total per circuit (25 Ω per wire); 0.1 µF capacitance per circuit
- Maximum IDC distance: 4,000 ft (1,219 m) to EOL resistor
- EOL resistor: 47 KΩ
- Weight: 0.4 lb (0.15 kg)
- Datasheet: Edwards / GE Security 85001-0241
Compatibility
The Edwards SIGA-CT1 communicates only with the Edwards Signature Loop Controller. Therefore, it works with Signature-equipped Edwards panels such as the EST3, EST3X, iO Series, and QuickStart-ES. Always confirm panel compatibility against the firmware revision in your system.
Important Application Note
The SIGA-CT1 will not support 2-wire smoke detectors. Specifically, it is designed only for dry-contact initiating devices and monitor inputs. For 2-wire smoke detection, use the appropriate Signature 2-wire smoke detector interface instead.
Order the Edwards SIGA-CT1
Life Safety Consultants stocks the Edwards SIGA-CT1 along with the Signature Series module family. To confirm the right personality code for your application or place an order, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.5 lbs |
|---|---|
| Dimensions | 2 × 2 × 2 in |
| Part Type | Single Input, Smoke Detector |
| Manufacturers | Edwards |
| Compatible Panels | EST3,EST3X,iO64,iO500,QuickStart QS1 |
| Cross Reference | SIGA-CT2,SIGA-CC1 |
| Input | 1 x supervised contact |
| Protocol | Edwards Signature SLC |
| Address | Single point |
| Supervision | Open and short |
| Mounting | Standard electrical box or Signature enclosure |