The Simplex 2088-9681 is a 1-inch chrome catch plate extension rod for electromagnetic door holders. Specifically, it lets the door holder catch plate sit farther off the door surface. As a result, you can correct mounting misalignment between the door-mounted armature and the wall-mounted electromagnet.
This rod is a door holder accessory. It is NOT a pull station part. Therefore, do not order it for pull station repair or replacement.
What the Simplex 2088-9681 Does
Electromagnetic door holders hold fire-rated doors open during normal building operations. Then, on a fire alarm signal, the panel drops power and the door swings closed. However, the catch plate on the door must align cleanly with the magnet face. Otherwise, holding force drops below the 25-lb minimum required by UL 228.
In real-world installations, door surfaces, frames, and magnet placement often do not match perfectly. As a result, you may need to push the catch plate forward by a fraction of an inch. The 2088-9681 adds exactly 1 inch of standoff between the door and the catch plate. Furthermore, the chrome finish keeps the part visually consistent with the matching chrome catch plate.
Key Features
- Length: 1 inch (25.4 mm)
- Finish: Chrome — matches standard chrome catch plate hardware
- Material: High-strength steel construction
- Threads to the back of the standard door holder catch plate
- Adjusts the standoff distance to restore proper magnet-to-plate contact
- Compatible with electromagnetic door holders used in NFPA 72 fire alarm systems
- Supports the 25-lb minimum holding force required under UL 228
Specifications
- Part type: Door holder catch plate extension rod
- Length: 1″
- Finish: Chrome (polished)
- Material: Steel
- Weight: Approximately 0.1 lb
- Compliance: NFPA 72; UL 228 (door holding device standard)
- Application: Electromagnetic door holders — interior commercial doors
Typical Applications
- Healthcare corridors with smoke-barrier doors
- School and university buildings with fire-rated doors
- Office and tenant-improvement work with retrofit door holders
- Stairwell access doors held open under normal operation
- Any installation where door-frame depth varies and the catch plate needs additional standoff
Other Available Lengths
Catch plate extension rods come in multiple lengths to fit different mounting situations. For thicker standoffs, see the 2088-9682 (3-inch). For shorter offsets, ask our team about 0.5-inch options. First, measure the gap between the door surface and the magnet face. Then, choose the rod length that closes the gap.
Order the Simplex 2088-9681
Life Safety Consultants stocks the Simplex 2088-9681 and the full range of door holder accessories. To confirm the right length for your job or place an order, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | .1 lbs |
|---|---|
| Dimensions | 1 × .25 × .25 in |
| Condition | New |
| Part Type | Door Holder Accessory |
| Manufacturers | Simplex |
| Compatible Panels | Simplex fire alarm systems controlling Simplex 2088-series electromagnetic door holders |
| Specification | 1in chrome extender rod, 0.25in diameter, door holder accessory, minimum 25 lb hold force, 0.1 lbs |