The Simplex 4098-9774 is the black-finish version of the TrueAlarm analog addressable photoelectric smoke sensor for IDNet and MAPNET II fire alarm systems. The 4098-9774 uses a pulsed infrared LED light source and silicon photodiode receiver to provide analog smoke measurements digitally transmitted to the host fire alarm control panel every four seconds. Seven sensitivity levels are selectable at the panel, ranging from 0.2% to 3.7% per foot of smoke obscuration. Sensitivities of 0.2%, 0.5%, and 1.0% are for special applications in clean areas; standard sensitivities are 1.5%, 2.0%, 2.5%, 3.0%, and 3.7%. The sensor operates from 32° to 122°F (0° to 50°C) UL listed range; air velocity rating is 0–4,000 ft/min (0–1,220 m/min). The 4098-9774 is UL 268 and ULC-S529 listed; CSFM listed; FM Approved; MEA (NYC) accepted. The 4098-9774 sensor head provides 360° smoke entry. Sensor dimensions: 4-7/8″ (124 mm) diameter × 2-1/8″ (54 mm) height. This is a commercial sensor; it will only function with a Simplex fire alarm system and will NOT operate as a stand-alone detector.
Key Features
- Black-finish TrueAlarm photoelectric sensor—white equivalent is 4098-9714
- Seven panel-selectable sensitivity levels: 0.2%, 0.5%, 1.0%, 1.5%, 2.0%, 2.5%, 3.0%, 3.7% per foot
- Pulsed IR LED source with silicon photodiode; 360° smoke entry
- IDNet or MAPNET II two-wire analog communications; auto-selected
- Air velocity rating: 0–4,000 ft/min (0–1,220 m/min)
- UL listed operating temperature: 32° to 122°F (0° to 50°C)
- UL 268 and ULC-S529 listed; FM Approved; CSFM listed; MEA (NYC) accepted
- Magnetic test feature; automatic environmental compensation
- Sensor dimensions: 4-7/8″ (124 mm) × 2-1/8″ (54 mm)
Compatible Panels
4007ES, 4010, 4010ES, 4100ES, 4100U (IDNet); 4020, 4100, 4120 Series with Universal Transponders; 2120 TrueAlarm CDTs (MAPNET II)
Compatible Bases
4098-9792 (white standard base), 4098-9776 (black standard base), 4098-9789, 4098-9775 (black), 4098-9791 (4-wire supervised relay base), 4098-9780 (2-wire supervised relay base)
Life Safety Consultants has supplied Simplex smoke detectors since 2002. For questions about the 4098-9774 or compatible bases, call 1-888-557-0558 or email sales@lifesafetycom.com.
Additional information
| Weight | .025 lbs |
|---|---|
| Dimensions | 4 × 4 × 2 in |
| Condition | New |
| Part Type | Photoelectric, Sensor, Smoke Detector |
| Manufacturers | Simplex |
| Compatible Panels | 4007ES, 4010, 4010ES, 4100ES, 4100U, 4020, 4100, 4120 Series, 2120 TrueAlarm CDTs |
| Compatible Bases | 4098-9792 4098-9776 4098-9789 4098-9775 4098-9791 4098-9780 |
| Specification | 7 sensitivity levels 0.2%-3.7%/ft, pulsed IR LED + photodiode, 32-122 deg F (0-50 deg C) UL listed, 0-4000 ft/min air velocity, UL 268 and ULC-S529 listed, FM Approved, CSFM listed, MEA (NYC), 4-7/8 in dia x 2-1/8 in H |